UPS runtime calculator

Enter your total load in watts or VA and how long it must run during a power cut. The calculator picks the right Ventrix Pro model and estimates the backup time, and the runtime chart shows every model at a glance.

1

Your load

Enter the total power of the equipment you want to protect, in watts or VA.

W

Add up the power of all the equipment you want to protect. You can find it on each device's label or datasheet. If the label shows VA, choose VA and we convert it: watts = VA × power factor.

2

Backup time needed

How long must the equipment keep running after the power goes off?

minutes
3

Options

Leave room for growth and choose a model, or let us recommend one.

All Ventrix Pro models at your load

ModelRatingBatteriesLoadEst. backupMeets your target?
Ventrix Pro 1K-RT1 kW2 × 9 Ah internal84%< 5 minNo, above 80% load
Ventrix Pro 2K-RT2 kW4 × 9 Ah internal42%14 minNo, too short
Ventrix Pro 3K-RT3 kW6 × 9 Ah internal28%23 minYes
Ventrix Pro 6K-RT6 kW1 pack14%55 minYes
Ventrix Pro 10K-RT10 kW1 pack8%1 h 14 minYes

Ventrix Pro runtime chart

Estimated backup time at different loads for each model, using the battery condition and temperature you selected above. Cells with “—” are above the model's rating.

ModelBatteries100 W250 W500 W750 W1 kW1.5 kW2 kW3 kW4 kW5 kW6 kW8 kW10 kWHalf loadFull load
1K-RT2×9Ah1h 19m26m11m5m< 5m————————11 min
500 W
< 5 min
1,000 W
2K-RT4×9Ah2h 59m1h26m16m11m5m< 5m——————11 min
1,000 W
< 5 min
2,000 W
3K-RT6×9Ah4h 45m1h 39m42m26m18m11m6m< 5m—————11 min
1,500 W
< 5 min
3,000 W
6K-RT1×(16×7Ah)10+h3h 51m1h 43m1h 3m44m27m19m12m7m< 5m< 5m——12 min
3,000 W
< 5 min
6,000 W
10K-RT1×(16×9Ah)10+h5h 7m2h 19m1h 25m1h37m26m16m11m7m5m< 5m< 5m7 min
5,000 W
< 5 min
10,000 W

Backup times are estimates for new, fully charged batteries at 25 °C, based on typical 12 V VRLA battery discharge data and inverter efficiency. Real runtime varies with battery age, temperature and the actual power drawn by your equipment, so allow a safety margin. Axtren recommends keeping the UPS load at or below 80% of its rating. Contact us to confirm sizing for critical sites or for longer backup times.

How is UPS backup time calculated?

The calculator adds up your equipment wattage (plus any growth margin), divides it by the UPS inverter efficiency and spreads it across the battery cells. It then reads the discharge time from typical constant-power data for 12 V VRLA batteries. More batteries or a smaller load give a longer backup time.

What is the difference between VA and watts?

VA (volt-amperes) is apparent power; watts are the real power your equipment uses. Watts = VA × power factor. Ventrix Pro UPS models have an output power factor of 1.0, so a 3 kVA model delivers up to 3,000 W.

How can I get a longer backup time?

Choose a 6K-RT or 10K-RT model and add external battery packs, or choose a larger UPS so the batteries discharge more slowly. For long-backup projects, contact Axtren sales for a sized battery configuration.

Why does battery age change the backup time?

Sealed lead-acid UPS batteries slowly lose capacity. After about three years they typically hold around 70% of their original charge, so the backup time drops. Test batteries every 6–12 months and replace them when the backup time is no longer enough.

Why should the UPS run at 80% or less?

Running below 80% leaves headroom for start-up surges and future equipment, keeps the UPS cooler and extends battery backup time.